5 MVA Oil Centrifuging & Transformer Service — Spectra International Limited
Project Overview
Ohmistiry performed comprehensive transformer servicing and oil centrifuging for a 5 MVA power transformer at Spectra International, restoring insulation quality and ensuring safe, efficient power supply for the facility.
Scope of Work
- Visual inspection of transformer tank, bushings, radiators, and conservator
- Transformer oil sampling and dielectric strength (BDV) testing
- Oil centrifuging to remove moisture, sludge, and particulate contamination
- Oil filtration and reconditioning post-centrifuging
- HV/LV terminal connection tightening
- Insulation resistance (IR) and winding resistance testing
- Buchholz relay and pressure relief device checks
- Earthing continuity inspection
- Thermal imaging to detect hotspots
- Final load and performance testing
Result
Oil centrifuging improved the transformer's dielectric strength and insulation performance, extending equipment life and protecting Spectra International against unplanned power failures.